Electrical features
Rated voltage |
kV |
12 |
17,5 |
24 |
Dielectric withstand voltage to earth and |
|
28 |
38 |
50 |
between phases (50 Hz 1 kV min) |
|
|
|
|
Impulse withstand voltage to earth and |
|
75 |
95 |
125 |
between phases (50 Hz 1 kV min ) |
|
|
|
|
Rated current |
A |
630 |
630 |
630 |
Breaking capacity of active circuits (cos f 0.7) and |
A |
630 |
630 |
630 |
ring circuits at 0.3 A |
|
|
|
|
Breaking capacity of no-load transformers |
A |
25 |
25 |
25 |
Brea Breaking capacity of no-load lines / cables |
A |
25 |
25 |
25 |
Short time current (1 s) - IMS(*) and earthing switch |
kA |
12,5÷25 |
12,5÷25 |
12,5÷25 |
Short time current (4 s) - IMS(*) |
kA |
12,5÷20 |
- |
- |
Making capacity - IMS(*) and earthing switch |
kA |
31,5÷62,5 |
31,5÷62,5 |
31,5÷62,5 |
Internal arc withstand current (0.5 s) |
kA |
12,5÷16 |
12,5÷16 |
12,5÷16 |
(*) IMS = switch-disconnector